ACTRONIC
®
Profibus DP Operating instructions
SideStep
®
Industrial Positioner
21/43
SetBasics
SpeedAdj
StartSpOpen 07D7 2007 Write [0..1000] *0.1 %
StartSpClose 07D8 2008 Write [0..1000] *0.1 %
StopSpOpen 07D9 2009 Write [0..1000,-1] *0.1 %
StopSpClose 07DA 2010 Write [0..1000,-1] *0.1 %
Force ADj
InitFOpen 07DB 2011 Write [0..550] *0.1 %
InitFClose 07DC 2012 Write [0..550] *0.1 %
ForceOpen 07DD 2013 Write [0..550] *0.1 %
ForceClose 07DE 2014 Write [0..550] *0.1 %
SetFunction
ProcCtrlMode * 0BB8 3000 Write 0: OFF
1: ON
DeadBand 0BB9 3001 Write [1..250] *0,1%
PwFailDir ** 0BBA 3002 Write 0: Close
1: Open
2: Hold
CpyParaSet 0BBB 3003 Write 0: OFF
1: P1<=W
2: P1=>P2
3: P1<=P2
4: P1=>P3
5: P1<=P3
6: P1=>P4
7: P1<=P4
ProcCtrl
Proc-P * 0C1C 3100 Write [0..1000]*0.1
Proc-I * 0C1D 3101 Write [0..9999]*0.1s
Proc-D * 0C1E 3102 Write [0..1000]*0.1
Proc-T * 0C1F 3103 Write [1..10 000] ms
IxType 0C20 3104 Write 0: OFF
1: RC
2: avr
IxFilter 0C21 3105 Write [10...2000] *0.01s
PosCtrl
Pos P 0C80 3200 Write [0..1000] *0.1
Pos D 0C81 3201 Write [0..1000] *0.1
Pos T 0C82 3202 Write [1..5000] ms
MinPos 0C83 3203 Write [0..1000] *0.1 %
MaxPos 0C84 3204 Write [0..1000] *0.1 %
closeTight 0C85 3205 Write [0..200] *0.1 %
openTight 0C86 3206 Write [800..1000] *0.1 %
TightTime 0C87 3207 Write [800..120,0] *0.1 s
* only available with integrated process controller version
** only available with emergency power supply module version