ACTRONIC
®
Profibus DP Operating instructions
SideStep
®
Industrial Positioner
9/43
7.6.1. No action
When using the “N” (NOP) instruction, no action is carried out. The response is another
NOP instruction.
Inquiry from the master:
0xYY 0x4E (“N“) 0x00, 0x00 0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x4E (“N“) 0x00, 0x00 0x00, 0x00, 0x00, 0x00
1 byte 1 byte 2 bytes 4 bytes
7.6.2. Change parameters
The “S“ (SET) instruction enables the change of a parameter in the SideStep via the
Profibus. As a response, the SideStep returns the SET instruction with the changed
parameter value. If the value is higher than the valid range, an external diagnostic error
with code 0x21 is generated; if below, the error generated has code 0x20.
Where the parameter does not exist, the diagnostic error triggered has code 0x22, and the
value returned is 0.
In case of a parameter change, the new value of the parameter is returned to the master
together with a SET instruction.
Where the parameter does not exist, the value returned is 0.
Inquiry from the master:
0xYY 0x53 (“S“) ID Value of the parameter
1 byte 1 byte 2 bytes 4 bytes
Response of the SideStep:
0xYY 0x53 (“S“) ID Value of the parameter
1 byte 1 byte 2 bytes 4 bytes
The individual parameters of the GEMÜ SideStep are on page 19.
Ex: The Mode parameter needs to be changed to Manual.
0xYY 0x53 (“S“) ID Value of the parameter
Mode Manual
0xYY 0x53 0x64 0x00, 0x00, 0x00, 0x02